« Reinforcement specifications of antiseismic design Minimum spacing between reinforcement bars » |
Reinforcement covering
The reinforcement covering is required for the following reasons:
a. Protection of reinforcement from corrosion (rusting).
b. The need for adequate adhesion between the steel and concrete.
c. Fire protection: the concrete that
covers reinforcement protects it from deformations caused by the
development of high temperatures due to fire in the building.
d. The need to create cable and pipe channels without harming the reinforcement [*]NoteThe
channel is the carving that an electrician or a plumber does in order
to engrave a recess channel in a structural element. Inside these
channels he places electric cables or pipes. Usually any electrical or
mechanical equipment should be planned ahead to be implemented inside
adequate pipes , or by designing recesses inside the concrete coating
thickness. Only when there a change in the initial planning should the
carving process be done. Even then, extra caution should be taken not to
‘cut’ any transverse or longitudinal reinforcement and to ensure that
these channels are smaller than the concrete coating thickness.
Generally coverings secured by the use of
plastic spacers have a considerable material pro-curement cost as
opposed to their low implementation cost.
Of course it is possible to use other
“common” materials as well, like pieces of marble. These although they
have a low procurement cost their implementation is economically
demanding. However, their largest problem is their correct application
since they are placed after the posi-tioning of reinforcement and prior
to the concrete casting.
In cases where visible concrete surfaces
(off-form concrete or architectural concrete) is re-quired, one may use
point or linear spacers made out of fiber reinforced concrete or even rebar chairs with fiber reinforced concrete tipped legs.
Covering of slabs lower reinforcement
The minimum required cover depth for slab
reinforcement usually ranges between 20 and 30 mm depended on the
environmental conditions present throughout the building’s service life.
The 20 mm would apply to a dry climate and the 30 mm to a seaside
location.
The required covering is achieved only with
the use of special stand-offs, called spacers. These must not be
affected by corrosion and should be placed approximately every 1.00 m.
The simplest solution for providing the
necessary cover depth of the reinforcement is special plastic spacers
like the ones shown in the above figure. Usage of steel rebar spacers is
forbid-den as they are highly susceptible to corrosion.
When rebars corrode the resulting volume
expansion leads to concrete spalling and conse-quently to the cracking
of the plaster. Extensive deterioration affects not only the occupants’
safety but also the structure’s service life.
Ensuring the slab’ upper reinforcement position
The position of the upper (negative) slab
reinforcement, either placed in the support between two slabs or in the
support between a slab and a balcony (cantilever slab), can be secured
only with the use of special rebar chairs.
In the continuous slab with the cantilever,
shown at the picture below, the proper upper rein-forcement positioning
is achieved by three ways:
(a) directly on the formwork with the use of rebar chairs
(b) indirectly with the use of folded mesh spacers
(c) indirectly with the use of S-shaped mesh spacers
Direct, rebar chair.
Prefabricated element, made out of a thin
steel rebar with plastic tipped legs in order to prevent corrosion of
the support area between the rebar chair and the formwork.
Indirect, S-shaped mesh spacer.
Prefabricated, comes in packages of straight lengths. It is formed in an S shape during the im-plementation.
Indirect, folded mesh spacer.
It is easily formed by folding wire of a
standard wire diameter mesh e.g. O/200, to the desirable height. In
cases of cantilevers apart from the spacer it can be used as “J-pin”
reinforcement, necessary for the cohesion of the free edges.
Indirect “J-pin” rebar chair.
For sheer use in slabs’ free edges.
In cases where mesh is used as upper
reinforcement in a slab support, its position can be se-cured with the
use of an S-shaped mesh spacer placed on the lower reinforcement grate
along the length of the plastic spacer.
In cases where support upper reinforcement
comes from bend up span rebars, its proper placement is achieved by the
reinforcement bending and therefore bar chairs might not be nec-essary.
Two indirect S-shaped mesh spacers are placed
to the left support of the continuous slab. These are fitted upon the
lower reinforcement grate along the length of the linear plastic
spac-ers.
In the right support (cantilever balcony) of
the above continuous slab, two rows of spacers are placed. The first row
consists of indirect folded mesh spacers fitted upon two longitudinal
plastic spacers and the second row consists of a number of direct rebar
chairs.
It is mandatory to prevent the folded mesh
spacer from lateral slipping and this can be achieved with the use of
local spacers. They must be placed right after the implementation of the
folded mesh spacer and prior to its tieing with the slabs’
reinforcement. When using disk spacers extra attention should be paid to
their vertical placement so as to avoid drifting during concreting.
However when they are used in slab edges (as shown in the above figure)
they can be horizon-tally placed since concrete does not fall directly
upon these areas.
Support of the negative slab’s reinforcement with indirect S-shaped mesh spacers and folded mesh spacers
Alternatively, when having a light-weight
steel mesh as the lower reinforcement of a cantilever it is recommended
to use indirect S-shaped mesh spacers instead of direct rebar chairs. In
that case it is more practical to place a “J-pin” mesh spacer inside
which the mesh will be properly positioned.
Another solution, even when there is
reinforcement mesh on the lower side of the slab or the cantilever, is
the use of direct rebar chairs rather than indirect S-shaped mesh
spacers.
Use of steel rebar chairs directly placed upon
the formwork is strictly forbidden and furthermore the use of old type
impromptu spacers is more expensive.
Beam reinforcement covering
The minimum required cover depth for beam
rebars usually ranges between 25 and 35 mm de-pended on the
environmental conditions present throughout the building’s service life.
The 25 mm applies to a dry climate and the 35 mm to a seaside location.
Beam stirrups should be supported at the base
of the beam, by a uniform inactive bar since all reinforcement loadings
are transferred to these areas.
Lateral cover depths should be created with
the use of special plastic spacers. When using stir-rup cage it is wiser
to place the disk spacers upon the connecting rebars in order to secure
their position during concrete casting.
Lateral spacers do not bear any loads,
therefore it not necessary for them to be heavy duty. Moreover they
should be placed after the implementation of the stirrup cage inside the
beam’s formwork and prior to the tieing of the beam’s rebars to the
slabs reinforcement.
The use of lateral longitudinal plastic bars
(like the ones placed at the bottom part of the beam) creates two
problems: a) it does not enable the implementation of the stirrup cage
inside the beam’s formwork and b) it obstructs the proper concrete
casting of the beam. If the stirrup cage has been industrially
producted, it will have secondary longitudinal connecting bars. In such a
case, pieces of vertically fitted plastic bars may be used.
Column reinforcement covering
The minimum required cover depth for column
rebars usually ranges between 25 and 35 mm depending on the
environmental conditions present throughout the building’s service life.
The 25 mm apply to a dry climate and the 35 mm to a seaside location.
Forming the desirable covering of column
reinforcement is quite a simple task. For example, four (4) individual
spacers placed at the column’s upper part, are enough since the column’s
base rebars are tied together in the lap-splice areas.
Especially for columns, the use of spacers for
creating the required cover depth helps in the proper centering of the
vertical rebars. Therefore when the reinforcement of the next storey is
being placed no extra time (with a corresponding additional cost) will
be spent in bringing the rebars to their proper position.
Covering can be secured either with disk
spacers placed on the upper part of rebars (in that area there is no
danger of drifting during the concreting) or with the use of vertical
disk spacers fitted upon the stirrups or finally with the use of plastic
pieces vertically positioned upon the formwork.
In every case though, spacers must be fitted
after the positioning of the stirrup cage in order to facilitate the
implementation of the cage and the proper centering of rebars.
Shear wall reinforcement covering
As far as the integrated columns of the shear
wall edges are concerned, the required cover depth is the same as the
columns’ reinforcement covering. As far as the wall body reinforce-ment
is concerned, its cover depth is created according to the following:
After forming the back of the wall, plastic
tracks are nailed upon the formwork. These tracks have a usual length
around 2.0 m and they can be used as one single piece or separate
smaller pieces.
After this, follows the implementation of the
column edge, of the body reinforcement and of the spacers that are
fitted upon the internal reinforcement grate. That way after the
placement of the formwork’s last piece the required cover depth and the
proper centering of the reinforcement will be secured.
After the reinforcement implementation and prior to ‘closing’ the shear wall’s formwork, the two plastic tracks are tied upon the inner reinforcement grate.
In shear walls the most effective way for
reinforcement implementation is to place the rein-forcement before the
assembling of the formwork. In that case, spacers are fitted upon the
re-bars.
Foundation reinforcement covering
The minimum required cover depth of the
foundation reinforcement is around 40 mm for founda-tion positioned on
ground leveling slab and around 70 mm for foundation positioned directly
upon the ground.
The construction of foundation directly upon
the ground’s surface is allowed only in special cas-es. The sub-slab
ensures many things like:
1) comfortable area to work on
2) capability of accurate marking of the areas of footings and columns
3) a stable substrate on top of which spacers will be placed
4) avoidance of a muddy foundation ground due to water usage or possible rain
The required covering may be created by point
or even better by linear spacers. Because of the weight they bear and
due to their required height, it is recommended to use heavy duty
spacers.
Use of spacers on the sides of the footings is
obligatory in order to prevent rebars from slipping. Since they do not
bear weight, they can be sparsely placed and they should be fitted
vertically to avoid drifting during the concreting process.
Ensuring the proper position of upper reinforcement in foundation slabs
In cases of total or partial raft foundation
or when constructing the bottom slab of a pool, the use of rebar grid as
upper reinforcement is necessary.
Just like in superstructure slabs, in the
areas around the slab edges, “J-pin” rebars may be combined with open or
closed reinforcement mesh.
In the intermediate area, the required cover
depth can be created with the use of special steel rebar chairs placed
on top of the lower reinforcement grate.
|
Search This Blog
Saturday, 21 January 2012
Subscribe to:
Post Comments (Atom)
No comments:
Post a Comment